Transformer Pad

USI Product Code
E14AK
Hydro One DL 21968C01
Dimensions
5" (H) x 62" x 75"
.125m (H) x 1580mm x 1900mm
Weight
1400 lbs
636 kg
Shop Drawings
Click on image to enlarge.
Construction Details
- AS PER HYDRO ONE DL 21968C01 (OLD SPEC)
- USE WITH BASE E14, E14-ONT, OR E14B-ONT
Product Details
- PAD OPENING: 44" [1118mm] x 58" [1473mm]
LOAD REQUIREMENTS
LOAD REQUIREMENTS
DISTRIBUTED LATERAL LOAD
25kN/m2
TOP SLAB DISTRIBUTED LOAD
60kN/m2
TOP SLAB POINT LOAD
70kN
Available Custom Options
- CUSTOM OPENINGS
CSA Details
CSA 23.4-05
- 35 MPa (5000psi) AT 28 DAYS
- STRIPPING STRENGTH: MIN. 20 MPa (2900psi)
- 5-8% AIR ENTRAINED
- EXPOSURE CLASS: C-1
REINFORCING: STEEL TO CSA CAN A23.1
Request More Information