Transformer Base

USI Product Code
E14-ONT
Hydro One DU-09-403
Dimensions
42" (H) x 62" x 75"
1.07m (H) x 1580mm x 1900mm
Weight
5600 lbs
2545 kg
Shop Drawings
Click on image to enlarge.
Construction Details
- REFERENCE HYDRO ONE DU-09-403
- USE WITH E14 (403) TRANSFORMER PAD
Product Details
- (4) 5" [127mm] POLYLOK PIPESEAL WINDOWS (12 POLYLOKS PER WINDOW)
- THREE PHASE PAD – MOUNTED SWITCHGEAR (4-WAY) TRANSFORMER BASE
- CLOSED BOTTOM VERSION AVAILABLE DWG# E14B-ONT
LOAD REQUIREMENTS
LOAD REQUIREMENTS
DISTRIBUTED LATERAL LOAD
25kN/m2
TOP SLAB DISTRIBUTED LOAD
60kN/m2
TOP SLAB POINT LOAD
70kN
Notes
- DISTRIBUTED AND POINT LOADS ON TOP SLAB SHALL NOT BE APPLIED SIMULTANEOUSLY
- SOIL BEARING CAPACITY TO BE MIN. 340kPA (SLS); VERIFY ON SITE
- THESE DRAWINGS ARE ONLY FOR STRUCTURAL. OTHER MATTERS INCLUDING GEOTECHNICAL AND DRAINAGE TO BE TAKEN CARE BY THE ENGINEERS OF THEIR RESPECTIVE DISCIPLINES
- TRANSFORMER ANCHORAGE FROM E14-ONT BASE THROUGH E14 (403) PAD FOR LATERAL LOADS (SEISMIC/WIND) BY OTHERS
Available Custom Options
- CUSTOM WINDOWS
- OPENINGS
CSA Details
CSA 23.4-05
- 35 MPa (5000psi) AT 28 DAYS
- STRIPPING STRENGTH: MIN. 20 MPa (2900psi)
- 5-8% AIR ENTRAINED
- EXPOSURE CLASS: C-1
REINFORCING: STEEL TO CSA CAN A23.1
Request More Information