Single Phase Transformer Pad

USI Product Code
E7
Hydro Ottawa UCS 0003
Dimensions
6" (H) x 51" x 51" (OD)
.15m (H) x 1300mm x 1300mm (OD)
Weight
975 lbs
445 kg
Shop Drawings
Click on image to enlarge.
Construction Details
- REFERENCE HYDRO OTTAWA UCS 0003
- TO BE USE WITH SINGLE PHASE DWG# E6 BASE
Product Details
- (4) 0.6" [15mm] DIAMETER INSERTS
- PAD OPENING: 30.5" [776mm] x 16" [413mm]
LOAD REQUIREMENTS
LOAD REQUIREMENTS
DISTRIBUTED LATERAL LOAD
25kN/m2
TOP SLAB DISTRIBUTED LOAD
60kN/m2
TOP SLAB POINT LOAD
70kN
Available Custom Options
- CUSTOM OPENINGS
CSA Details
CSA 23.4-05
- 35 MPa (5000psi) AT 28 DAYS
- STRIPPING STRENGTH: MIN. 20 MPa (2900psi)
- 5-8% AIR ENTRAINED
- EXPOSURE CLASS: C-1
REINFORCING: STEEL TO CSA CAN A23.1