[lwp_divi_breadcrumbs _builder_version=”4.17.0″ _module_preset=”default” global_colors_info=”{}”][/lwp_divi_breadcrumbs]
Single Phase Transformer Base and Pad

USI Product Code
E6+E7 Combo
Hydro Ottawa UCS 0003
Dimensions
60" (H) x 51" x 51" (OD)
1.52m (H) x 1300mm x 1300mm (OD)
Weight
4000 lbs
1815 kg
Shop Drawings
Click on image to enlarge.
Construction Details
- REFERENCE HYDRO OTTAWA UCS 0003
- E6 BASE AND E7 PAD ASSEMBLED
Product Details
- (4) 5" [127mm] POLYLOK PIPESEAL WINDOWS (9 POLYLOKS PER WINDOW)
- SINGLE PHASE BASE 25kVA TO 167kVA
- CLOSED BOTTOM KINGSTON UTILITIES VERSION AVAILABLE DWG# E6B
- (4) 0.6" [15mm] INSERTS IN E7 PAD
- PAD OPENING: 30.5" [776mm] x 16" [413mm]
LOAD REQUIREMENTS
LOAD REQUIREMENTS
DISTRIBUTED LATERAL LOAD
25kN/m2
TOP SLAB DISTRIBUTED LOAD
60kN/m2
TOP SLAB POINT LOAD
70kN
Available Custom Options
- CUSTOM WINDOWS
- OPENINGS
CSA Details
CSA 23.4-05
- 35 MPa (5000psi) AT 28 DAYS
- STRIPPING STRENGTH: MIN. 20 MPa (2900psi)
- 5-8% AIR ENTRAINED
- EXPOSURE CLASS: C-1
REINFORCING: STEEL TO CSA CAN A23.1
Request More Information